    Effect of polyacrylate inhibitors on weakly acidic cation-exchanger at water treatment plants processing blowdown of circulating cooling systems.

  • Authors

    Shulyak I. D.

  • Subject

    ENERGETICS. HEAT ENGINEERING. ELECTRICAL ENGINEERING

  • Year 2013
    Issue 3(42)
    UDC 621.182.475
    DOI
    Pages 81-85
  • Abstract

    The influence of different concentrations of polyacrylate inhibitor Acumer 1000 on weakly acidic cation-exchanger at water treatment plants processing blowdown of circulating cooling systems is experimentally studied. It is shown that the inhibitor concentrations in the range of 0...1 mg/dm3 have little effect on cation resin exchange capacity, at inhibitor concentrations above 3 mg/dm3 cation resin exchange capacity decreases sharply. Quantity of water been treated before the breakthrough point — 1.4 mg-eq/dm3 in experiments with varying concentrations of acrylate inhibitor in the source water, ceteris paribus at concentrations above 2 mg/dm3 decreases sharply. With increasing inhibitor content in the treated water the expected hardness breakthrough time is distinctly reduced. It is demonstrated that the presence of the inhibitor in the treated water does not affect the kinetics of hardness sorption process. The curve of dependence is flatter inherent for weakly acidic cation resins. The results obtained are recommended for use when designing water treatment plants with series weakly acidic cation-exchanging filters prior to RO plants for the separation of the mass-saline flow into two, each of which (permeate and concentrate) may at its composition comply with the standards, imposed on makeup water of station cycles.

  • Keywords
  • Viewed: 1058 Dowloaded: 0
  • Download Article
  • References

    1.Kavitha, A.L. Evaluation of synthesized antiscalants for cooling water system application / A.L Kavitha, T.Vasudevan, H.Gurumallesh Prabu // Desalination. - 2011. - № 268. - P. 38 - 45.

    2.Кишневский,В.А. Методика расчета водно-химического режима комплексной оборотной системы охлаждения с рециркуляцией / В.А.Кишневский, В.В.Чиченин, И.Д.;Шуляк//  Восточно-Европ.;журн. передовых технологий. - 2013. - № 6(66).- С. 10-14.

    3.Репин, Д.А. Влияние ОЭДФК и хеламина на работу катионитных фильтров/ Д.А. Репин, Т.И.Петрова // Пятнадцатая междунар. научн.-техн. конф. студентов и аспирантов ;Радиоэлектроника, электротехника и энергетика: Тез. докл. - М., 2009. - Т. 3. - С. 172 - 173.

    4.Исследование работы сильнокислотного катионита в контакте с комплексными аминосодержащими реагентами / Д.Н. Мелентьев, А.В. Кирилина, С.Ю. Суслов, И.А. Сергеев // Междунар. научн.-техн. конф. Водоподготовка и водно-химические режимы ТЭС. Цели и задачи Тез. докл. - 2013- С. 129 - 139.

    5.Применение гибридных водоподготовительных установок при обработке продувочных вод оборотных систем охлаждения / В.А. Кишневский, Е.В. Кишневский, О.М. Малиновский, И.Д. Шуляк // Вода и водоочист. технологии. Науч-техн.вести-2011. - №-2(4). с. 53-58.

  • Creative Commons License by Author(s)